  • Safety switch with integrated evaluation electronics
  • Possible to switch pulsed signals
  • 2 safety outputs (semiconductor outputs)
  • Category 3/PL e according to EN ISO 13849-1
  • Unicode
Approach directionCan be adjusted in 90° steps Each actuator is unique. The switch detects only taught-in actuators. Additional actuators can be taught in. Category according to EN ISO 13849-1Due to two redundantly designed semiconductor outputs (safety outputs) with internal monitoring suitable for:
  • Category 3/PL e according to EN ISO 13849-1
LED indicator
STATEStatus LED
OUT/ERRORSafety outputs status / diagnostics LED (combined)
Additional connection
OUTMonitoring output (semiconductor)
Typical operating distancesAttention:The operating distance may vary depending on the background material and installation situation. (Only in combination with actuator CES-A-BBA, CES-A-BCA) Typical operating distance For a side approach direction for the actuator and safety switch, a minimum distance of s = 4 mm must be maintained so that the operating distance of the side lobes is not entered. (Only in combination with actuator CES-A-BPA) Typical operating distance For a side approach direction for the actuator and safety switch, a minimum distance of s = 6 mm must be maintained so that the operating distance of the side lobes is not entered.
Dimensions According to EN 60947-5-2: (LxWxH) 131x40x40
Housing material Plastic, PBT
Weight
Net 0,4 kg
Ambient temperature
At UB = 24 V DC -20 ... 55 °C
Degree of protection IP67
Mounting distance
Between 2 switches or 2 actuators min.80 mm
Installation orientation Any
Tightening torque
Screws fastening bracket read head max.0,6 Nm
Fixing screws housing max.1 Nm
Ready delay max.3 s
Reaction time
After change in the actuation status max.180 ms
Switching frequency max.1 Hz
Dwell time min.0,5 s
Connection M12 plug connector, 8-pin, screen can be applied
Electrical connection ratings
Operating voltage DC 18 ... 24 ... 27 V DC Regulated, residual ripple < 5 %
Current consumption 80 mA
Fusing
(External) operating voltage 0,25 ... 8 A
Rated insulation voltage Ui 300 V
Rated impulse withstand voltage Uimp max.1,5 kV
EMC protection requirements In acc. with EN 60947-5-3
Degree of contamination (external, according to EN 60947-1) 3
Safety outputs LA / LB
Type of output Semiconductor outputs, p-switching, short circuit-proof, electrically decoupled
Output voltage
HIGH U(LB) U(+LB) - 1,5 ... U(+LB) V DC
LOW U(LA) / U(LB) 0 ... 1 V DC
HIGH U(LA) U(+LA) - 1,5 ... U(+LA) V DC
Output current
per safety output 1 ... 400 mA
Fusing
External, safety circuit U(+LA) / U(+LB) 0.4 A medium slow-blow
Utilization category according to EN 60947-5-2
DC-13 24V 400mA
Switching load
According to UL max. DC 24 V, class 2
Rated conditional short-circuit current max.100 A
Discrepancy time
(Between the operating points of both safety outputs) max.120 ms
Power supply output load
U(+LA) / U(+LB) 24 V DC 18 ... 27 V DC
Monitoring output OUT
Type of output Semiconductor output, p-switching, short circuit-proof
Output voltage 0,8 x UB ... UB V DC
Output current max.20 mA
STATE LED
LED indicator Status LED
LED OUT / ERROR
LED indicator Safety outputs status / diagnostics LED (combined)
Work area
Repeat accuracy R max.10 %
Other
For the approval according to UL the following applies Operation only with UL class 2 power supply, or equivalent measures
Reliability values according to EN ISO 13849-1
Monitoring of the safety guard position
Category 3
Performance Level PL e
PFHD 4.29 x 10-8
Diagnostic Coverage (DC) 90 %
Mission time 20 y
In combination with Actuator CES-A-BBA, CES-A-BCAOperating distance
Distance s, actuator
Minimum distance for side approach direction min.4 mm
Switch-on distance
With center offset m=0 20 mm
Assured switch-off distance Sar max.40 mm
Assured operating distance Sao
With center offset m=0 min.18 mm
Switching hysteresis min.2 mm
In combination with Actuator CES-A-BPAOperating distance
Distance s, actuator
Minimum distance for side approach direction min.6 mm
Switch-on distance
With center offset m=0 22 mm
Assured switch-off distance Sar max.58 mm
Assured operating distance Sao
With center offset m=0 min.15 mm
Switching hysteresis min.1 mm
In combination with Actuator CES-A-BDA-20Operating distance
Distance s, actuator
Minimum distance for side approach direction min.5 mm
Switch-on distance
With center offset m=0 21 mm
Assured switch-off distance Sar max.41 mm
Assured operating distance Sao
With center offset m=0 min.19 mm
Switching hysteresis min.2 mm
''