Описание

  • For connecting MGB2 or MCM modules
  • Interface to PROFINET/PROFIsafe
  • Connection via plug connector RJ45, AIDA compliant
  • Remote or direct mounting
  • Integrated switch
  • Compatible with all Modular devices
PROFINET interface Plug connector RJ45 AIDA-compliant (push-pull plug according to IEC 61076-3-117, variant 14) PROFINET switch Linear topology network structure due to integrated switch (supports MRP). MLI connections (module plug connector) An MGB2 Modular or an MCM Modular can be connected directly to a bus module (direct plug). Alternatively, the modules can be connected using commercially available connecting cables M12, 5-core (cable connect). Dimension drawing Dimension drawing MGB2 Modular: an overview Dimension drawingDimension drawing Technical dataApprovals Mechanical values and environment
Housing material Fiber glass reinforced plastic, die-cast zinc, nickel plated
Weight
Net 0,8 kg
Ambient temperature
At UB = 24V DC -25 ... 55 °C
Degree of protection IP65
Resilience to vibration In acc. with EN 60947-5-3
Installation orientation Any
Connection Push-pull power
According to IEC 61076-3-117 variant 14, screened, Profinet I/O cable, at least cat. 5e Push-pull RJ45
Push-pull RJ45
Push-pull power
ML1C / ML2C
Type specification M12 EN 61076-2-101 / A-coded
Insertion cycles 100
Connection Screw terminal
Connection type Plug
Number of pins 5
ML1D
Insertion cycles 100
Connection Connector (unlocked)
Connection type Plug
Number of pins 5
Electrical connection ratings
Current consumption max.150 mA
Rated insulation voltage Ui 75 V
Rated impulse withstand voltage Uimp 1,5 kV
Maximum feed-in current in the connection block
XD1, XD2 max.16000 mA
EMC protection requirements EMC directive 2014/30/EU
Degree of contamination (external, according to EN 60947-1) 3
Connecting cable
MLI 5-pin, M12x1
Safety class III
Interface, bus
Data interface
Data protocol
Safety protocol Profisafe (IEC 61784-3-3)
Bus protocol Profinet (IEC 61158 type 10)
Reliability values according to EN ISO 13849-1
Performance Level PL e
PFHD 1.14 x 108
Safety Integrity Level SIL 3 (EN 62061:2005)
Mission time 20
''