Описание

Function Residual current monitor, Type A
Type of voltage AC, DC pulsierend
Adjustable measuring ranges 0,01 ... 10, 0,01 ... 30 A
Relay contact / output +
Operate delay +
Test key +
Clear key +
Broken conductor detection +
Enclosure design Installationsverteiler
Width 35 mm
Type IL 5882
According to IEC/EN 62 020 for AC and pulsating DC currants Type A to IEC/TR 60755 9 tripping values from 10 mA to 10 A or from 10 mA ... 30 A Frequency range 20 ... 2000 Hz Selection of manual or automatic reset With prewarning With test and reset button Broken wire detection Short reaction time With adjustable delay tv De-energized on trip LED indication for auxiliary supply and state of contact 2 x 1 changeover contact With sealable cover Devices available in 3 enclosure versions:IL 5882: 63 mm deep with terminals near to the bottom to bemounted in consumer units or industrial distributionsystems according to DIN 43 880- width 35 mm- for connection of external residual current transformer,e. g. DOLD ND 5016, ND5019''